Simulasi Koordinasi Kinerja Proteksi Phase Overcurrent Relay Berbasis Fuzzy Logic Menggunakan ETAP 7.5 (Studi Pada PT. Pupuk Kujang Cikampek)

MUHAMMAD IRFAN ARDIANSYAH, . (2014) Simulasi Koordinasi Kinerja Proteksi Phase Overcurrent Relay Berbasis Fuzzy Logic Menggunakan ETAP 7.5 (Studi Pada PT. Pupuk Kujang Cikampek). Sarjana thesis, UNIVERSITAS NEGERI JAKARTA.

[img] Text
4. BAB SATU.pdf

Download (39kB)
[img] Text
1. COVER.pdf

Download (73kB)
[img] Text
5. BAB DUA.pdf

Download (462kB)
[img] Text
3. DAFTAR ISI.pdf

Download (46kB)
[img] Text
9. DAFTAR PUSTAKA.pdf

Download (73kB)
[img] Text
8. BAB LIMA.pdf

Download (33kB)
[img] Text
7. BAB EMPAT.pdf

Download (498kB)
[img] Text
10. LAMPIRAN.pdf

Download (1MB)
[img] Text
6. BAB TIGA.pdf

Download (681kB)
[img] Text
12. BIOGRAFI.pdf
Restricted to Registered users only

Download (44kB)

Abstract

Metode fuzzy logic memberikan solusi yang praktis untuk mengendalikan suatu sistem serta memberikan rangka kerja yang kuat dalam memecahkan masalah pengontrolan. Oleh karena itu pada penelitian ini akan diuraikan koordinasi proteksi phase overcurrent relay berbasis fuzzy logic untuk menentukan waktu operasi (td) relay tersebut dan selisih waktu operasi (td) antar relay yang berdekatan. Metode yang digunakan pada penelitian ini adalah metode penelitian simulasi. Data-data equipment sistem tenaga listrik pada PT. PKC yang akan diolah diperoleh melalui proses wawancara dan observasi. Pemodelan sistem kelistrikan PT. PKC dalam bentuk single line diagram dilakukan pada software ETAP 7.5. Sedangkan pemodelan variabel input dan output fuzzy logic dilakukan pada software MATLAB. Tipikal koordinasi fuzzy yang dirancang terbagi menjadi tiga tipikal koordinasi yaitu, tipikal koordinasi 1, 2 dan 3. Variabel lingusitik yang terkumpul pada tipikal koordinasi fuzzy tersebut adalah “CEPAT”, “SEDANG”, “LAMBAT”, “SANGAT LAMBAT”. Kemudian dilakukan simulasi gangguan hubung singkat pada tipikal koordinasi fuzzy tersebut menggunakan software ETAP 7.5 dengan tujuan untuk melihat respon phase overcurrent relay secara aktual. Simulasi dilakukan menggunakan gangguan hubung singkat tiga fasa di empat titik gangguan yang tersebar pada tipikal kordinasi yang telah dipilih, mulai dari bus beban motor pada bus 63-MCC-2 dan 63-MCC-3B hingga bus outgoing utama 63-LBS-1A. Berdasarkan hasil simulasi di setiap titik gangguan menunjukkan bahwa koordinasi kinerja phase overcurrent relay berbasis fuzzy logic mampu menentukan waktu operasi (td) berdasarkan variabel lingusitk yang telah dirancang dan memiliki selisih waktu operasi (td) antar relay yang berdekatan berdasarkan gradasi linguistik dari variabel linguistik yang dirancang. Dengan demikian maka phase overcurrent relay berbasis fuzzy logic mampu menggantikan metode konvensional dalam menentukan waktu operasi (td) relay dan selisih waktu operasi (td) antar relay yang berdekatan berdasarkan prinsip gradasi level proteksi main protection dan backup protection *Fuzzy logic method provides practical solutions to contol a system and present a solid work design in order as a problem solver in controlling field. So, this research will dechiper the protection coordination performance of phase overcurrent relay based on fuzzy logic to determine time operation (td) and time difference between the rearest relay of phase overcurrent relay. Simulation research method is proposed in this paper. Electrical equipment data of PT. PKC is modeled by single line diagram in ETAP 7.5. However, input and output variable of fuzzy logic are modeled with MATLAB. The design of fuzzy typical coordination separate into three typical coordination. Typical coordination 1, 2 and 3. Linguistic variable that use here are “FAST”, “NORMAL”, “SLOW” and “VERY SLOW”. Then, short circuit fault simulation will held in ETAP 7.5, in order to see the actual responses of phase overcurrent relay coordination. The fault simulation will held is three phase short circuit. Fault simulation conducted in four fault spots which spread in typical coordination that have choosen. Start from load motor bus in bus 63-MCC-2 and 63- MCC-3B until main outgoing bus 63-LBS-1A. Based on simulation results in each fault spots, the protection coordination performance of phase overcurrent relay based on fuzzy logic was able to determine time operation (td) based on linguistic variable which was designed and so on, able to determine time difference between the nearest phase overcurrent relay based on linguistic gradation of linguistic variable which was designed. So, phase overcurrent relay based on fuzzy logic is able to replace the conventional method in order to determine time operation (td) and time difference between the nearest relay of phase overcurrent relay based on principal of gradation level of main and back up protection

Item Type: Thesis (Sarjana)
Additional Information: 1). Aris Sunawar S.pd, M.T. ; 2). Muhammad Rif’an S.T, M.T.
Subjects: Teknologi dan Ilmu Terapan > Teknik Elektronika
Divisions: FT > S1 Pendidikan Teknik Elektro
Depositing User: Users 8922 not found.
Date Deposited: 09 May 2022 01:53
Last Modified: 09 May 2022 01:53
URI: http://repository.unj.ac.id/id/eprint/27686