PENGUJIAN HOUSE LOAD OPERATION MODE (HLOM) SEBAGAI RESPONS TERHADAP BLACKOUT BERBASIS SIMULASI PADA APLIKASI ELECTRICAL TRANSIENT AND ANALYZER PROGRAM (ETAP) VERSI 19.0.1 (STUDI PADA PLTGU BLOK 4 UPJP PRIOK)

MUHAMMAD WILDAN ALQOVARI, . (2025) PENGUJIAN HOUSE LOAD OPERATION MODE (HLOM) SEBAGAI RESPONS TERHADAP BLACKOUT BERBASIS SIMULASI PADA APLIKASI ELECTRICAL TRANSIENT AND ANALYZER PROGRAM (ETAP) VERSI 19.0.1 (STUDI PADA PLTGU BLOK 4 UPJP PRIOK). Sarjana thesis, UNIVERSITAS NEGERI JAKARTA.

[img] Text
COVER.pdf

Download (1MB)
[img] Text
BAB I.pdf

Download (615kB)
[img] Text
BAB II.pdf
Restricted to Registered users only

Download (1MB) | Request a copy
[img] Text
BAB III.pdf
Restricted to Registered users only

Download (3MB) | Request a copy
[img] Text
BAB IV.pdf
Restricted to Registered users only

Download (3MB) | Request a copy
[img] Text
BAB V.pdf
Restricted to Registered users only

Download (601kB) | Request a copy
[img] Text
DAFTAR PUSTAKA.pdf

Download (618kB)
[img] Text
LAMPIRAN DAN DAFTAR RIWAYAT HIDUP.pdf
Restricted to Registered users only

Download (4MB) | Request a copy

Abstract

Penelitian ini bertujuan untuk mensimulasikan pengujian House Load Operation Mode (HLOM) pada PLTGU Blok 4 UPJP Priok dengan menggunakan perangkat lunak Electrical Transient and Analyzer Program (ETAP) versi 19.0.1. Metode yang digunakan adalah metode deskriptif kuantitatif dengan pendekatan studi simulasi berdasarkan data hasil pengujian aktual di lapangan yang kemudian dimodelkan dan dianalisis secara dinamis melalui ETAP. Hasil simulasi menunjukkan bahwa sistem PLTGU Blok 4 mampu mempertahankan stabilitas transien selama proses pemutusan dan transisi ke mode house load, ditandai dengan tetap sinkronnya kecepatan generator yang kembali di 3000 rpm setelah terjadi kenaikan di 3125 rpm serta tegangan bus yang kembali stabil di 50 Hz setelah terjadi kenaikan ke 51,5 Hz tetapi masih berada dalam batas toleransi. Simulasi ini memberikan gambaran yang komprehensif terhadap perilaku sistem selama HLOM dan menjadi acuan penting dalam pengembangan strategi pengamanan dan keandalan operasi pembangkit. Dengan demikian, penelitian ini dapat menjadi kontribusi dalam meningkatkan kesiapan sistem tenaga listrik menghadapi kondisi darurat melalui pendekatan berbasis simulasi. ***** This study aims to simulate the testing of House Load Operation Mode (HLOM) at PLTGU Block 4 UPJP Priok using the Electrical Transient and Analyzer Program (ETAP) version 19.0.1. The research method employed is a descriptive quantitative approach with a simulation based study, utilizing actual field test data that is then modeled and dynamically analyzed through ETAP. The simulation results show that the PLTGU Block 4 system is capable of maintaining transient stability during the disconnection process and the transition to house load mode, this is indicated by the generator speed, which remained synchronized by returning to 3000 rpm after increasing to 3125 rpm, and the bus frequency, which stabilized at 50 Hz after increasing to 51.5 Hz, both of which remained within acceptable tolerance limits. This simulation provides a comprehensive overview of system behavior during HLOM and serves as an essential reference for developing protection strategies and ensuring power plant operational reliability. Therefore, this research contributes to improving the readiness of the power system in facing emergency conditions through a simulation based approach.

Item Type: Thesis (Sarjana)
Additional Information: 1). Drs. Readysal Monantun, M.Pd. ; 2). Massus Subekti, S.Pd., MT.