ANALISA PENGARUH RUGI-RUGI DAN EFISIENSI TRANSFORMATOR DISTRIBUSI TERHADAP TEGANGAN JATUH PADA GARDU DISTRIBUSI TENAGA LISTRIK DI PT. PLN (PERSERO) AREA JARINGAN MARUNDA.

AHMAD HADI, . (2014) ANALISA PENGARUH RUGI-RUGI DAN EFISIENSI TRANSFORMATOR DISTRIBUSI TERHADAP TEGANGAN JATUH PADA GARDU DISTRIBUSI TENAGA LISTRIK DI PT. PLN (PERSERO) AREA JARINGAN MARUNDA. Sarjana thesis, UNIVERSITAS NEGERI JAKARTA.

[img] Text
abstrak.pdf

Download (31kB)
[img] Text
BAB I.pdf

Download (52kB)
[img] Text
BAB II.pdf

Download (8MB)
[img] Text
BAB III.pdf

Download (153kB)
[img] Text
BAB IV.pdf

Download (4MB)
[img] Text
BAB V.pdf

Download (29kB)
[img] Text
Lampiran depan.pdf

Download (474kB)
[img] Text
Lampiran belakang.pdf

Download (2MB)
[img] Text
JURNAL-AHMADHADI-5115096957.pdf

Download (2MB)
[img] Text
DAFTAR PUSTAKA.pdf

Download (14kB)

Abstract

Penelitian ini bertujuan untuk membuktikan adanya pengaruh rugi-rugi dan efisiensi transformator distribusi terhadap tegangan jatuh (drop voltage) pada sistem distribusi tenaga listrik di PT. PLN (Persero) Area Marunda pada bulan Februari - Maret 2014. Penelitian dilakukan dengan metode obeservasi lapangan diawali dengan pengumpulan data serta teori yang berhubungan dengan penelitian selanjutnya dilakukan pengukuran pembebanan ke 9 gardu distribusi yang terdapat pada penyulang Sarapan. Pengukuran dilakukan pada saat siang dan malam hari dan data-data yang diambil adalah Besar Tegangan dan Besar Arus di setiap feeder gardu distribusi. Setelah dilakukan pengukuran pembebanan transformator serta mengukur tegangan ujung. Selanjutnya, akan dilakukan proses perhitungan rugi-rugi transformator dan besar tegangan jatuh yang terjadi pada jaringan distribusi pada 9 gardu. Gardu PK 231 yang jaringan distribusinya berjarak 1813 m saat siang hari memiliki besar Pembebanan Transformator 213,010 KVA dengan Rugi Total 1,686 KW serta besar Efisiensi Transformator 99,076 % dan Tegangan Jatuh (drop voltage) yang terjadi pada jaringan sebesar 19 V. Sedangkan saat malam, besar Pembebanan Transformator 300,156 KVA dengan Rugi Total 2,768 KW serta besar Efisiensi Transformator 98,927 % dan Tegangan Jatuh yang terjadi pada jaringan sebesar 26 V. Kesimpulan dari penelitian ini adalah setelah mendapatkan hasil penghitungan pada gardu PK 231, efisiensi transformator distribusi saat siang dan malam hari masih diatas 98,84 % atau masih dalam standar PLN. Namun besar Tegangan Jatuh (drop voltage) jaringan distribusi PK 231 saat malam hari sebesar 26 V (10,9704%) atau melebihi standar PLN sebesar 10 % dari toleransi yang diberikan standar PLN. ***** This research aims to prove there it can impact of losses and efficiency distribution of transformation to drop voltage in PT. PLN (Persero) area Marunda on this february – march 2014, using observation research method. The research have been done using observation research method with collect data and theori that connected with the research continue to load measurement to 9 electrical distribution substation in Penyulang Sarapan. The measurement done in the mid day and in the night which datas needed is voltages dan currents in every feeder of distribution substation. After measured load transformation and volatge receive. And then calculated losses and efficiency transformation 9 distribution substation, known that the transformer loading at nightgreter appeal during the day. Substation distribution PK 231 network which is 1813 m during the day time has transformer loading 213,010 KVA with a total losses 1,686 KW, efficiency of the transformer is 99,076 % and drop voltage that occurs on the network is 19 V. While at night, transformer loading 300,156 KVA with a total losses 2,768 KW, efficiency transformer is 98,927 % and drop voltage that occurs on a network is 26 V. The summary of this research is after getting the result of calculation on substation PK 231, distribution transformer efficiency when day and night are still above 98,84 or still on PLN standard. However drop voltage of distribution network in PK 231 at night is 26V (10,9704%) still exceeds the standard on above 10% of the tolerance that is given PLN standard.

Item Type: Thesis (Sarjana)
Additional Information: .
Subjects: Teknologi dan Ilmu Terapan > Teknik Energi > Energi Listrik
Teknologi dan Ilmu Terapan > Teknik Energi
Divisions: FT > S1 Pendidikan Teknik Elektro
Depositing User: PKL .
Date Deposited: 18 Nov 2026 07:04
Last Modified: 18 Nov 2026 07:04
URI: http://repository.unj.ac.id/id/eprint/76296

Actions (login required)