SIGID RACHMADI YUWONO, . (2021) ANALISIS OVERHEATING PADA PERALATAN LISTRIK PHB-TR GARDU DISTRIBUSI DI PT. PLN (PERSERO) ULP DEPOK KOTA MENGGUNAKAN TERMOGRAFI INFRAMERAH. Sarjana thesis, UNIVERSITAS NEGERI JAKARTA.
Text
COVER.pdf Download (821kB) |
|
Text
BAB 1.pdf Download (220kB) |
|
Text
BAB 2.pdf Restricted to Registered users only Download (1MB) | Request a copy |
|
Text
BAB 3.pdf Restricted to Registered users only Download (580kB) | Request a copy |
|
Text
BAB 4.pdf Restricted to Registered users only Download (2MB) | Request a copy |
|
Text
BAB 5.pdf Restricted to Registered users only Download (204kB) | Request a copy |
|
Text
DAFTAR PUSTAKA.pdf Download (348kB) |
|
Text
LAMPIRAN.pdf Restricted to Registered users only Download (1MB) | Request a copy |
Abstract
Salah satu faktor penyebab gangguan PHB-TR adalah adanya degradasi material pada peralatan listrik yang dapat menyebabkan panas berlebih (overheating) dan mengakibatkan terjadinya kegagalan peralatan yang berpotensi menyebabkan pemadaman listrik yang tidak direncanakan dan bahaya kebakaran. Proses terjadinya degradasi pada peralatan listrik dapat disebabkan oleh berbagai faktor seperti beban berlebih (overload), kondisi lingkungan, dan lain-lain. Tujuan dari penelitian ini adalah untuk mengetahui apakah terdapat overheating pada peralatan listrik PHB-TR gardu distribusi di area distribusi PT. PLN (Persero) ULP Depok Kota, untuk menganalisis tingkat kesesuaian suhu permukaan peralatan listrik PHB-TR dengan SPLN D3.016-1:2010 dan SPLN D3.016-2:2013, dan untuk menganalisis faktor-faktor apa saja yang dapat menyebabkan terjadinya overheating pada peralatan listrik PHB-TR gardu distribusi. Dalam rangka mengetahui kondisi suhu permukaan peralatan listrik PHB-TR yang diteliti, maka dilakukan pengukuran suhu permukaan objek penelitian secara langsung menggunakan termografi inframerah. Kemudian data hasil pengukuran suhu tersebut dibandingkan dengan standar SPLN D3:016-1:2010 dan SPLN D3.016-2:2013. Metode penelitian yang digunakan dalam penelitian ini adalah deskriptif kuantitatif. Hasil penelitian dari empat gardu distribusi diantaranya gardu RJM, gardu DTG, gardu CLD, dan gardu KCL menunjukkan bahwa terdapat overheating pada peralatan listrik PHB-TR dari seluruh gardu distribusi tersebut. Gardu KCL memiliki tingkat kesesuaian suhu permukaan peralatan listrik PHB-TR lebih rendah dibandingkan tiga gardu distribusi lainnya yakni dengan tingkat kesesuaian 83%. Sedangkan gardu DTG memiliki tingkat kesesuaian suhu permukaan peralatan listrik PHB-TR lebih tinggi dibandingkan tiga gardu distribusi lainnya yakni dengan tingkat kesesuaian 99%. Kesimpulan dari hasil penelitian pada proses pengukuran suhu permukaan peralatan listrik PHB-TR gardu distribusi menggunakan termografi inframerah di area distribusi PT. PLN (Persero) ULP Depok Kota adalah overheating pada peralatan listrik PHB-TR dapat disebabkan oleh kondisi permukaan peralatan penghantar yang telah mengalami proses penuaan dan pengaruh lingkungan, adanya ketidakseimbangan beban antar fasa, pemasangan peralatan listrik yang tidak sesuai standar, dan pemasangan peralatan pemutus beban yang tidak memperhatikan faktor keamanan untuk beban trafo distribusi. One of the factors causing PHB-TR breakdown is material degradation in electrical equipment which can cause overheating and result in equipment failure which has the potential to cause unplanned power outages and fire hazards. The process of degradation of electrical equipment can be caused by various factors such as overload, environmental conditions, and others. The purpose of this study was to determine whether there was overheating of the PHB-TR electrical equipment at the distribution substation in the distribution area of PT. PLN (Persero) ULP Depok City, to analyze the level of suitability of the surface temperature of PHB-TR electrical equipment with SPLN D3.016-1:2010 and SPLN D3.016-2:2013, and to analyze what factors can cause overheating in PHB-TR electrical equipment at distribution substations. In order to determine the condition of the surface temperature of the PHB-TR electrical equipment under study, the surface temperature of the research object was measured directly using infrared thermography. Then the temperature measurement data is compared with the standard SPLN D3:016-1:2010 and SPLN D3.016-2:2013. The research method used in this research is quantitative descriptive. The results of the research from four distribution substations including RJM substation, DTG substation, CLD substation, and KCL substation indicate that there is overheating in the PHB-TR electrical equipment from all the distribution substations. The KCL substation has a lower level of suitability for the surface temperature of the PHB-TR electrical equipment compared to the other three distribution substations with a suitability level of 83%. Meanwhile, the DTG substation has a higher level of suitability for the surface temperature of PHB-TR electrical equipment than the other three distribution substations, with a suitability level of 99%. The conclusion from the results of research on the process of measuring the surface temperature of electrical equipment PHB-TR distribution substations using infrared thermography in the distribution area of PT. PLN (Persero) ULP Depok Kota is overheating in PHB-TR electrical equipment can be caused by surface conditions of the delivery equipment that have undergone an aging process and environmental influences, load imbalances between phases, installation of electrical equipment that does not meet standards, and installation of load breaker equipment which does not pay attention to the safety factor for distribution transformer loads.
Item Type: | Thesis (Sarjana) |
---|---|
Additional Information: | 1). Drs. Ir. Parjiman, M.T. ; 2). Massus Subekti, S.Pd., M.T. |
Subjects: | Teknologi dan Ilmu Terapan > Teknik Energi > Energi Listrik Teknologi dan Ilmu Terapan > Teknologi (umum) |
Divisions: | FT > S1 Pendidikan Teknik Elektro |
Depositing User: | Users 12995 not found. |
Date Deposited: | 18 Oct 2021 02:29 |
Last Modified: | 18 Oct 2021 02:29 |
URI: | http://repository.unj.ac.id/id/eprint/20939 |