ANALISIS PELUANG HEMAT ENERGI MELALUI AUDIT ENERGI PADA RUMAH SAKIT MULYA TANGERANG

KHUSWATUN HASANAH, . (2023) ANALISIS PELUANG HEMAT ENERGI MELALUI AUDIT ENERGI PADA RUMAH SAKIT MULYA TANGERANG. Sarjana thesis, UNIVERSITAS NEGERI JAKARTA.

[img] Text
COVER.pdf

Download (2MB)
[img] Text
BAB 1.pdf

Download (463kB)
[img] Text
BAB 2.pdf
Restricted to Registered users only

Download (1MB) | Request a copy
[img] Text
BAB 3.pdf
Restricted to Registered users only

Download (481kB) | Request a copy
[img] Text
BAB 4.pdf
Restricted to Registered users only

Download (756kB) | Request a copy
[img] Text
BAB 5.pdf
Restricted to Registered users only

Download (235kB) | Request a copy
[img] Text
DAFTAR PUSTAKA.pdf

Download (461kB)
[img] Text
LAMPIRAN.pdf
Restricted to Registered users only

Download (2MB) | Request a copy

Abstract

Penggunaan energi listrik yang tinggi perlu diperhatikan agar dapat mengefisiensikan tingkat konsumsi energi listrik. Salah satu cara dengan menggunakan audit energi yang bertujuan untuk mengetahui penggunaan energi listrik serta mencari upaya yang perlu dilakukan untuk peningkatan efisiensi penggunaan energi listrik pada suatu bangunan. Penelitian ini dilakukan di Rumah Sakit Mulya Tangerang. Penelitian ini bertujuan untuk mengetahui besarnya peluang penghematan energi listrik pada sistem pencahayaan dan sistem pendingin udara. Dengan menggunakan metode penelitian deskriptif untuk mengetahui kondisi tingkat pencahayaan yang ada pada ruangan-ruangan rumah sakit dengan kriteria menurut SNI 6197:2011 dan suhu ruangan rumah sakit dengan kriteria menurut Kementrian Kesehatan Republik Indonesia No 1204/MENKES/SK/X/2004. Hasil penelitian menunjukan bahwa tingkat pencahayaan serta suhu yang diukur pada ruangan-ruangan masih kurang sesuai dengan standar. Hal tersebut menjadi dasar untuk mencari peluang penghematan. Dengan menyesuaikan kebutuhan lumen lampu dan kebutuhan kapasitas pendinginan sesuai dengan beban pendinginan ruangan, maka diperlukan skenario penghematan. Pada skenario penghematan sistem pencahayaan yaitu dengan mengganti lampu, menunjukkan penghematan energi sebesar 27.502,63 kWh pertahun dengan efisiensi penggunaan sebesar 2,7553%. Pada skenario penghematan sistem pendingin udara yaitu dengan mengganti AC, menunjukkan penghematan energi sebesar 171.612 kWh pertahun dengan efisiensi penggunaan sebesar 17,19%. Sehingga total penghematan energi dari kedua skenario sebesar 199.114,63 kWh pertahun. Dengan nilai IKE yang didapatkan yaitu 8,15 kWh/m2/bulan yang masuk dalam kategori efisien. Maka dapat disimpulkan bahwa dari skenario yang didapatkan berhasil memperoleh penghematan energi sebesar 19,94%. ****** The use of high electrical energy needs to be considered in order to be able to streamline the level of electrical energy consumption. One way is to use an energy audit which aims to find out the use of electrical energy and look for efforts that need to be made to increase the efficiency of the use of electrical energy in a building. This research was conducted at Mulya Hospital, Tangerang. This study aims to determine the magnitude of the opportunity for saving electrical energy in the lighting system and air conditioning system. By using descriptive research methods to determine the conditions of lighting levels in hospital rooms with criteria according to SNI 6197:2011 and hospital room temperature with criteria according to the Ministry of Health of the Republic of Indonesia No.1204/MENKES/SK/X/2004. The results showed that the lighting level and temperature measured in the rooms were not up to standard. This is the basis for looking for savings opportunities. By adjusting the lumen requirement of the lamps and the cooling capacity requirements according to the room’s cooling load, a savings scenario is needed. In the lighting system saving scenario, namely by replacing the lamp, it shows energy savings of 27.502,63 kWh/year with a usage efficiency of 2,7553%. In the scenario of saving the air conditioning system by replacing the air conditioner, it shows energy saving of 171.612 kWh/year with a usage efficiency of 17,19%. So the total energy savings from both scenarios is 199.114,63 kWh/year. The IKE value obtained is 8,15 kWh/m2/month which is included in the efficient category. So it can be concluded that from the scenario obtained managed to obtain an energy savings of 19,94%.

Item Type: Thesis (Sarjana)
Additional Information: 1) Massus Subekti, S.Pd., M.T. 2) Imam Arif Rahardjo, S.Pd., M.T.
Subjects: Teknologi dan Ilmu Terapan > Teknik Energi > Energi Listrik
Divisions: FT > S1 Pendidikan Teknik Elektro
Depositing User: Users 16809 not found.
Date Deposited: 21 Feb 2023 02:35
Last Modified: 21 Feb 2023 02:35
URI: http://repository.unj.ac.id/id/eprint/36933

Actions (login required)

View Item View Item