SIMULASI SISTEM PENCAHAYAAN PADA LANTAI 4 GEDUNG CENTER FOR DEVELOPMENT OF CHARACTER EDUCATION (STUDI KASUS MASJID KAMPUS A UNIVERSITAS NEGERI JAKARTA)

ILHAM WILLEM WAKUM, . (2024) SIMULASI SISTEM PENCAHAYAAN PADA LANTAI 4 GEDUNG CENTER FOR DEVELOPMENT OF CHARACTER EDUCATION (STUDI KASUS MASJID KAMPUS A UNIVERSITAS NEGERI JAKARTA). Sarjana thesis, UNIVERSITAS NEGERI JAKARTA.

[img] Text
COVER.pdf

Download (497kB)
[img] Text
BAB I.pdf

Download (363kB)
[img] Text
BAB II.pdf
Restricted to Registered users only

Download (1MB) | Request a copy
[img] Text
BAB III.pdf
Restricted to Registered users only

Download (529kB) | Request a copy
[img] Text
BAB IV.pdf
Restricted to Registered users only

Download (1MB) | Request a copy
[img] Text
BAB V.pdf
Restricted to Registered users only

Download (164kB) | Request a copy
[img] Text
DAFTAR PUSTAKA.pdf

Download (228kB)
[img] Text
LAMPIRAN.pdf
Restricted to Registered users only

Download (1MB) | Request a copy

Abstract

Penelitian ini bertujuan untuk mensimulasikan sistem pencahayaan di lantai 4 Gedung CDCE, khususnya terkait dengan apakah pencahayaan yang dihasilkan memenuhi standar yang ditetapkan dalam SNI. Pendekatan yang digunakan adalah kuantitatif deskriptif, dengan pengumpulan data melalui penggunaan luxmeter dan aplikasi Dialux Evo 13.1. Hasil simulasi menunjukkan bahwa lampu downlight 20,5 watt belum mampu memenuhi standar SNI 6197:2020, yang mengharuskan pencahayaan mencapai 200 lux. Pada waktu shubuh, maghrib, dan isya, rata-rata pencahayaan yang tercatat hanya 178,44 lux. Pada waktu dzuhur dan ashar, pencahayaannya masih di bawah batas minimum, dengan angka tertinggi mencapai 198,11 lux pada waktu dzuhur dengan kondisi langit cerah. Sebaliknya, penggunaan kombinasi lampu spotlight 20,5 watt dan floodlight 95 watt menghasilkan pencahayaan yang jauh lebih optimal. Rata-rata pencahayaan mencapai 242,83 lux pada kondisi tanpa cahaya alami, dan bahkan mencapai 329,38 lux pada dzuhur cerah. Berdasarkan hasil temuan ini, disarankan untuk mengganti sistem pencahayaan dengan kombinasi spotlight dan floodlight, serta merancang ulang posisi lampu untuk memastikan distribusi cahaya yang lebih merata, sehingga dapat meningkatkan kenyamanan dan mendukung kegiatan ibadah dengan lebih baik. ***** This study aims to simulate the lighting system on the 4th floor of the CDCE Building, specifically to determine whether the produced illumination meets the standards set by SNI. The approach used is descriptive quantitative, with data collection conducted through a lux meter and the Dialux Evo 13.1 application. The simulation results indicate that the 20.5-watt downlight does not meet the SNI 6197:2020 standard, which requires illumination to reach 200 lux. During Fajr, Maghrib, and Isha prayer times, the recorded average illumination was only 178.44 lux. During Dhuhr and Asr, the illumination remained below the minimum threshold, with the highest recorded value reaching 198.11 lux at Dhuhr under clear sky conditions. In contrast, the combination of a 20.5-watt spotlight and a 95-watt floodlight resulted in significantly better lighting. The average illumination reached 242.83 lux in the absence of natural light and even reached 329.38 lux during a bright Dhuhr. Based on these findings, it is recommended to replace the lighting system with a combination of spotlights and floodlights and redesign the lamp placement to ensure a more even light distribution, thereby enhancing comfort and better supporting worship activities.

Item Type: Thesis (Sarjana)
Additional Information: 1). Drs. Readysal Monantun, M.Pd. ; 2). Dr. Aris Sunawar, S.Pd., M.T.
Subjects: Teknologi dan Ilmu Terapan > Teknik Energi > Energi Listrik
Divisions: FT > S1 Pendidikan Teknik Elektro
Depositing User: Ilham Willem Wakum .
Date Deposited: 19 Feb 2025 01:48
Last Modified: 19 Feb 2025 01:48
URI: http://repository.unj.ac.id/id/eprint/53078