RIZKY NAHDATUL, . (2024) STUDI EKSPERIMENTAL PENGUJIAN THERMOSYPHON DENGAN VARIASI FILLING RATIO UNTUK APLIKASI PADA SISTEM PENGKONDISIAN UDARA. Sarjana thesis, UNIVERSITAS NEGERI JAKARTA.
Text
COVER.pdf Download (1MB) |
|
Text
BAB 1.pdf Download (262kB) |
|
Text
BAB 2.pdf Restricted to Registered users only Download (633kB) | Request a copy |
|
Text
BAB 3.pdf Restricted to Registered users only Download (618kB) | Request a copy |
|
Text
BAB 4.pdf Restricted to Registered users only Download (652kB) | Request a copy |
|
Text
BAB 5.pdf Restricted to Registered users only Download (227kB) | Request a copy |
|
Text
DAFTAR PUSTAKA.pdf Download (264kB) |
|
Text
LAMPIRAN.pdf Restricted to Registered users only Download (517kB) | Request a copy |
Abstract
Seiring dengan pembangunan pesat saat ini sistem Heating, Ventilation & Air Conditioning (HVAC) merupakan penggunaan energi yang signifikan dan penyumbang energi terbesar yaitu 40-60%. Hal tersebut menunjukan diperlukan sebuah efsiensi energi salah satunya Thermosyphon Heat Exchanger (THE) yang dapat mengurangi konsumsi energi. Penelitian ini bertujuan untuk mengetahui pengaruh filling ratio terhadap kinerja thermosyphon tunggal dan efektivitas thermosyphon untuk mengurangi konsumsi energi pada sistem HVAC. Pada penelitian ini kinerja thermal didapatkan dari hasil pengujian thermosyphon tunggal sedangkan untuk mengetahui pengaruh terhadap penghematan energi di sistem HVAC dilakukan dengan analisis teoritis menggunakan Sp number. Penelitian ini menggunakan metode eksperimental dengan menggunakan thermosyphon tunggal dan memvariasikan filling ratio fluida, yaitu 20, 30, 40, dan 50% serta menggunakan fluida kerja acetone dan pengujian dilakukan pada temperatur 30, 35, 40, 45, dan 50℃. Thermosyphon terbuat dari pipa tembaga dengan spesifikasi ∅10 mm, 700 mm. Hasil penelitian menunjukan tahanan thermal terbaik terjadi pada variasi FR 20% yaitu 0,27℃/W pada temperatur 50℃. Berdasarkan tahanan thermal tersebut, efektifitas tertinggi yang dihasilkan dari analisis teoritis Sp number diperoleh 6,87% pada pengujian 9 baris dengan kecepatan 2,5(m/s). Hasil analisis kinerja thermosyphon menunjukkan bahwa semakin kecil tahanan thermal pada thermosyphon, semakin baik efektivitasnya, dan konsumsi energi listrik pada sistem HVAC menjadi lebih rendah. Kata kunci: Energi recovery, filling ratio, heat exchanger, Sistem HVAC, thermosyphon. Along with the rapid development of today's Heating, Ventilation & Air Conditioning (HVAC) system is a significant energy use and the largest energy contributor of 40-60%. This shows that an energy efficiency is needed, one of which is Thermosyphon Heat Exchanger (THE) which can reduce energy consumption. This study aims to determine the effect of filling ratio on the performance of a single thermosyphon and the effectiveness of thermosyphon to reduce energy consumption in HVAC systems. In this study, thermal performance was obtained from the results of a single thermosyphon test while to determine the effect on energy savings in the HVAC system was carried out by theoretical analysis using Sp number. This research uses an experimental method using a single thermosyphon and varying the fluid filling ratio, namely 20, 30, 40, and 50% and using acetone working fluid and testing is carried out at temperatures of 30, 35, 40, 45, and 50 ℃. Thermosyphon is made of copper pipe with specifications ∅10 mm, 700 mm. The results showed that the best thermal resistance occurred in the 20% FR variation, which was 0.27℃/W at 50℃. Based on the thermal resistance, the highest effectiveness resulting from the theoretical analysis of Sp number was obtained 6.87% in the 9-line test with a speed of 2.5 (m/s). The results of the thermosyphon performance analysis show that the smaller the thermal resistance of the thermosyphon, the better its effectiveness. Keywords: Recovery energy, filling ratio, heat exchanger, HVAC system, thermosyphon.
Item Type: | Thesis (Sarjana) |
---|---|
Additional Information: | 1). Dr. Ragil Sukarno, M.T. 2). Dr. Eko Arif Syaefudin, M.T. |
Subjects: | Teknologi dan Ilmu Terapan > Teknik Energi Teknologi dan Ilmu Terapan > Manufaktur |
Divisions: | FT > S1 Pendidikan Teknik Mesin |
Depositing User: | Users 21637 not found. |
Date Deposited: | 31 Jan 2024 07:09 |
Last Modified: | 31 Jan 2024 07:09 |
URI: | http://repository.unj.ac.id/id/eprint/43933 |
Actions (login required)
View Item |