DEWI SETIYO NINGRUM, . (2017) ANALISIS TEGANGAN JATUH LISTRIK (DROP VOLTAGE) PADA JARINGAN TEGANGAN MENENGAH DI PENYULANG CITARUM (Studi dilakukan di PT PLN (Persero) Distribusi Jawa Barat Rayon Babelan). Sarjana thesis, UNIVERSITAS NEGERI JAKARTA.
Text
SKRIPSI DEWI SETIYO 5115122617.pdf Download (10MB) |
Abstract
Tujuan penelitian ini yaitu untuk mengetahui seberapa besar tegangan jatuh yang terjadi pada penyulang Citarum di Wilayah PT. PLN (Persero) Distribusi Jawa Barat Rayon Babelan sesuai SPLN No. 72 tahun 1987 dan mencari penyelesaian tegangan jatuh tersebut. Metode penelitian yang digunakan adalah metode deskriptif dengan cara survey dan rancangan penelitian melalui software Etap 12.6. Proses pengumpulan data dengan cara melakukan pengukuran tegangan dan beban pada PHB TR transformator distribusi dengan menggunakan tang ampere. Hasil penelitian tegangan jatuh pada penyulang Citarum sebesar 19.185% untuk hasil pada software Etap 12.6 dan 18.768% untuk hasil perhitungan secara manual. Rata-rata besar tegangan jatuh antara hasil simulasi Etap 12.6 dan hasil perhitungan manual sebesar 18.954%. Hasil tegangan jatuh pada penyulang Citarum, mengakibatkan terdapat 90 transformator yang menerima tegangan tidak sesuai standar dan hanya 5 transformator yang menerima tegangan sesuai standar. Solusi yang disarankan berupa memperbesar penampang penghantar dan pemindahan beban ke penyulang lain. The purpose of this study is to determine how much voltage drop occurs in feeder Citarum Territory PT. PLN (Persero) Distribution West Java Rayon Babelan according SPLN No. 72 in 1987 and search a solution to overcome the voltage drop. The method used is descriptive method by means of observation and study design through software Etap 12.6. The process of data collection by measuring the voltage and the load on the distribution transformer TR PHB using pliers ampere. Results of research on the feeder Citarum voltage drop of 19.185% of the yield on software Etap 12.6 and 18.768% for the calculation results manually. The average voltage drop between the simulation results Etap 12.6 and the results of the manual calculation of 18.954%. Results voltage drop in feeder Citarum, there is a 90 lead transformer which receives a voltage not fit the standard and only 5 transformer which receives standard voltage. The suggested solution in the form of a cross-conductor enlarge and transfer the load to another feeder.
Item Type: | Thesis (Sarjana) |
---|---|
Additional Information: | 1) Dr. Daryanto, M.T 2) Drs. Ir. Parjiman, M.T |
Subjects: | Teknologi dan Ilmu Terapan > Teknik Elektronika |
Divisions: | FT > S1 Pendidikan Teknik Elektro |
Depositing User: | sawung yudo |
Date Deposited: | 28 Jun 2022 05:08 |
Last Modified: | 28 Jun 2022 05:08 |
URI: | http://repository.unj.ac.id/id/eprint/30831 |
Actions (login required)
View Item |